Plan Review Notes For Permit 16110034 |
Permit Number |
16110034 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-18 08:24:05 | 1ST REVIEW FBC-2014 RESIDENTIAL, ENERGY CONSERVATION | | CODES | | PERMIT #16110034 | | 11/18/16 | | | | 1) PLEASE REMOVE THE AC CHANGE OUT FORM FROM THE PERMIT | | FILE- THIS IS NOT A CHANGE OUT- IT IS A NEW AC SYSTEM | | TO BE INSTALLED IN A PREVIOUSLY UNCONDITIONED RESIDENCE | | (SEE ATTACHED PAPA REPORT). | | | | 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY | | CONSERVATION: COMPLIANCE WITH THE CURRENT ENERGY CODE | | IS REQUIRED. PLEASE SEE SECTION R401.2 FOR COMPLIANCE | | OPTIONS AND SUBMIT ENERGY CALCULATIONS. | | | | 3) AC PLAN: A) IDENTIFY ALL ROOMS ON THE PLAN. B) | | PROVIDE A NORTH ARROW ON THE PLAN. C) INDICATE HOW AIR | | IS BEING RETURNED FROM THE BEDROOMS AND ANY OTHER | | RESTRICTED ZONES- M1602.4 FBC-14 RESIDENTIAL. | | | | 4) PROVIDE A CONDENSATE DISPOSAL PLAN- SHOW THE PRIMARY | | CONDENSATE PIPING RUN AND DISCHARGE LOCATION, AND THE | | SECONDARY MEANS- SECTION M1411.3. | | | | 5) THE SUBMITTAL FOR THE FATBOY ANCHOR CLIP HAS A | | COPIED ENGINEER'S SIGNATURE AND SEAL. AN ENGINEER IS | | REQUIRED TO PLACE AN ORIGINAL SIGNATURE AND SEAL ON ANY | | DESIGN HE/SHE IS REPONSIBLE FOR- SECTION 61G15-23.002 | | FLORIDA ADMINISTRATIVE CODE. | | | | 6) PROVIDE AN ELECTRICAL PLAN. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|