2016-11-03 11:08:32 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13. | | | | 24.2 ACCEPTANCE REQUIREMENTS. | | 24.2.1* HYDROSTATIC TESTS. | | | | 24.2.1.4 MODIFICATIONS AFFECTING 20 OR FEWER SPRINKLERS | | SHALL NOT REQUIRE TESTING IN EXCESS OF SYSTEM WORKING | | PRESSURE. | | | | 24.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS | | RELOCATED DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF | | SYSTEM WORKING PRESSURE. | | | | | | | | 2) PLEASE ENSURE THAT FIRE PUMP TEST PRESSURES ARE | | CALCULATED FOR WORKING PRESSURE. | | | | 24.2.1.2 PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO | | SYSTEM WORKING PRESSURES IN EXCESS OF 150 PSI (10.4 | | BAR) SHALL BE TESTED AS DESCRIBED IN 24.2.1.1, AT A | | PRESSURE OF 50 PSI (3.5 BAR) IN EXCESS OF SYSTEM | | WORKING PRESSURE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | |
|