2016-11-03 17:04:46 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16110011 | | 11/3/16 | | | | 1) THE CORRIDOR CANNOT BE USED TO CONVEY RETURN AIR- | | SECTION 601.2. PROVIDE A DUCTED RETURN FROM THE STORAGE | | ROOM. | | | | 2) THE FLEX DUCT RETURNING 150 CFMS OF RETURN AIR FROM | | THE BAR AREA APPEARS TO BE MISLABELED AS 12" INSTEAD OF | | 8". | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|