Plan Review Notes For Permit 16100953 |
Permit Number |
16100953 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-12-13 15:22:26 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT 316100953 | | 12/13/16 | | | | 1) A NEW AC SYSTEM IS SPECIFIED ON THE PLAN: A) CORRECT | | THE NOTE INDICATING "EX AHU". B) PROVIDE THE SEER OF | | THE SYSTEM IN THE SCHEDULE AND THE CORRECT SUPPLY CFMS | | FOR THE 4-TON UNIT. | | | | 2) THE 0.7CFM PER SQ. FT. LISTED ON THE O/A CALCULATION | | IS AN EXHAUST RATE, PLEASE CORRECT IF NO EXHAUST IS | | BEING PROVIDED. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|