Plan Review Notes
Plan Review Notes For Permit 16100953
Permit Number 16100953
Review Stop P
Sequence Number 1
Notes
Date Text
2016-11-17 17:31:181ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE 1 COMPARTMENT SINK SHALL DRAIN INTO THE GREASE
 INTERCEPTOR.PER FBC PL 1003.1
  
 2. PROVIDE WATER RISER. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
 3. LAVATORY IN PUBLIC BATHROOM REQUIRE TEMPERED WATER.
 PER FBC PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 4. BACKFLOW DEVICE REQUIRED ON ICE MACHINE COFFEE MAKER
 ANY APPLIANCE CONNECTED TO WATER. PER FBC PL 608.16.10
 COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS.
 THE WATER SUPPLY CONNECTION TO COFFEE MACHINES AND
 NONCARBONATED BEVERAGE DISPENSERS SHALL BE PROTECTED
 AGAINST BACKFLOW BY A BACKFLOW PREVENTER CONFORMING TO
 ASSE 1022 OR BY AN AIR GAP.608.3 DEVICES,
 APPURTENANCES, APPLIANCES AND APPARATUS.
 DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS
 INTENDED TO SERVE SOME SPECIAL FUNCTION, SUCH AS
 STERILIZATION, DISTILLATION, PROCESSING, COOLING, OR
 STORAGE OF ICE OR FOODS, AND THAT CONNECT TO THE WATER
 SUPPLY SYSTEM, SHALL BE PROVIDED WITH PROTECTION
 AGAINST BACKFLOW AND CONTAMINATION OF THE WATER SUPPLY
 SYSTEM. WATER PUMPS, FILTERS, SOFTENERS, TANKS AND
 OTHER APPLIANCES AND DEVICES THAT HANDLE OR TREAT
 POTABLE WATER SHALL BE PROTECTED AGAINST CONTAMINATION.
  
 5. ON THE COVER SHEET IN THE SCOPE OF WORK UNDER
 PLUMBING IT CALLS OUT A 35GPM ON SHT.3.0P IT CALLS OUT
 A 25 GPM PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 6. PROVIDE MANUFACTURE SIZING CALCULATION FOR GREASE
 INTERCEPTOR. PERPER WPB AMEND TO FBC 107.2.1
  
 7.SHT. 1.0A ENLARGE ACCESSIBILITY DETAIL IT IS
 DIFFICULT TO READ. WPB AMEND TO FBC 107.2.1.4 QUALITY
 OF BUILDING PLANS. BUILDING PLANS SHALL BE DRAWN TO A
 MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS
 FOR PLANS AND SPECIFICATIONS, IN
 ORDER TO PROVIDE CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF
 FLORIDA STATUTES.
  