Plan Review Notes For Permit 16100953 |
Permit Number |
16100953 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-03 15:06:55 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING. | | PERMIT #16100953 | | 11/3/16 | | | | 1) THE PROPOSED CAFE IS A CHANGE OF OCCUPANCY FROM THE | | PREVIOUS HAIR SALON AS DEFINED IN SECTION 202 FBC-14 | | EXISTING BUILDING. COMPLIANCE WITH THE CURRENT ENERGY | | CODE IS REQUIRED PER SECTION C101.4.4 FBC-14 ENERGY | | CONSERVATION. SEE SECTION C401.2 FOR COMPLIANCE PATH | | OPTIONS. | | | | 2) SHEET 3.1M: PROVIDE THE MAKE AND MODEL OF THE | | EXISTING AC SYSTEM AND THE COOLING AND HEATING | | CAPACITIES. | | | | 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | PROVIDED CFMS OF OUTDOOR AIR. | | | | 4) KITCHEN EXHAUST IS REQUIRED AT A RATE OF 0.7 CFMS | | PER SQ. FT. IN ACCORDANCE WITH TABLE 403.3 FBC-14 | | MECHANICAL- PROVIDE DETAILS ON THE PLAN. | | | | 5) IT APPEARS THAT NO AIR IS BEING SUPPLIED TO THE | | CORRIDOR. HOW IS THAT AREA TO BE VENTILATED? | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|