2016-11-04 10:12:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PERMIT VALUE IS TOO LOW. VALUE IS TO INCLUDE ALL
 LABOR, MATERIALS, OVERHEAD, PROFIT, EVEN IF PROVIDED BY
 OTHERS, FBC 109.
  
 2. SEE FIRE COMMENTS. BUSINESS OCCUPANCY IS THE CORRECT
 CLASSIFICATION FOR FLORIDA BUILDING CODE COMPLIANCE, SO
 RATHER THAN CHANGE THE OCCUPANCY CLASSIFICATION PLEASE
 ADD THE CORRECT FIRE OCCUPANCY CLASSIFICATION, FBC
 303.1.2.
  
 3. OCCUPANT LOAD SHOULD BE DETERMINED IN ACCORDANCE
 WITH FBC TABLE 1004.1.2 UNLESS THE SEATING IS FIXED.
 REVISE PLAN TO STATE WHETHER THE SEATING IS FIXED OR
 NOT, AND IF NOT, CALCULATE THE OCCUPANT LOAD AS PER THE
 TABLE.
  
 4. ACCESSIBLE SEATING AND CHECK OUT COUNTER NOT SHOWN,
 REVISE PLAN TO PROVIDE APPLICABLE DETAILS, FBC 5TH
 EDITION ACCESSIBILITY 226, 227, 902, 904.
  
  