Plan Review Notes
Plan Review Notes For Permit 16100914
Permit Number 16100914
Review Stop E
Sequence Number 1
Notes
Date Text
2016-11-21 14:57:361ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. PLANS ARE INLEGIBLE.
  
 2] THE SCOPE OF WORK, JOB ADDRESS, & APPLICABLE CODE
 SHALL APPEAR ON THE DRAWINGS ALONG WITH THE NAME &
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. FBC
 107.2.1