Plan Review Notes For Permit 16100911 |
Permit Number |
16100911 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-11-29 09:16:59 | COMMENTS FROM THE PREVIOUS PLUMBING PLAN REVIEW HAVE | | NOT BEEN ADDRESSED. | | 1) THE REVISION APPEARS TO BE FOR SUITE 100A TO BE | | TURNED INTO A SHELL SPACE ON THE ARCHITECTURAL SHEETS | | WHEREAS THE M1.1, P1.1, E1.1 & E1.2 STILL SHOW WALLS | | WHERE THE RESTROOM AND MECHANICAL CLOSET WERE REMOVED | | ON THE ACHITECTURAL SHEET. DISCREPANCY IN PLANS | | 107.2.1.3. 2ND REQUEST. | | 2) SANITARY FACILITIES ARE REQUIRED IN SUITE 100A PER | | FBC - PLUMBING SEC. 403.2 AND TABLE 403.1 FOR A | | MERCANTILE OCCUPANCY. THE SANITARY FACILITIES SHALL | | COMPLY WITH FBC ACCESSIBILITY. 2ND REQUEST. | | 3) A SERVICE SINK IS REQUIRED IN SUITE 100A PER | | FBC-PLUMBING TABLE 403.1. 2ND REQUEST | | 4) A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED IN | | SUITE 100A PER FBC-PLUMBING TABLE 403.1 FOOTNOTE # (E) | | AND FBC-ACCESS. SEC. 211.2.2ND REQUEST | | 5) SUBMIT A SANITARY AND WATER RISER FOR THE REQUIRED | | PLUMBING FIXTURES IN SUITE 100A. 2ND REQUEST. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|