2017-09-07 12:50:07 | 3RD REVIEW FBC-2014 MECHANICAL |
| PERMIT #16100893 |
| 9/7/16 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| COMMENTS FROM THE 2ND REVIEW STILL EXIST. I HAVE |
| REPRINTED THEM BELOW THE 3RD REVIEW COMMENTS. PLEASE |
| COMPLY WITH BOTH THE 2ND AND 3RD REVIEW COMMENTS. |
| |
| 1) M.1 & M.2: THE LAUNDRY ROOM (SYSTEM 7) IS NOT SHOWN |
| ON THE PLANS OR INCLUDED IN THE SCHEDULE- SEE AC AND |
| ENERGY CALCULATIONS. |
| |
| 2) THE ENERGY CALCULATION FORM R405-2014 MUST BE SIGNED |
| BY THE OWNER/AGENT. |
| |
| 3) THE WIND LOAD DESIGN CRITERIA AND ENGINEERING FOR |
| THE EXTERIOR CONDENSER AHOWN ON M.2 CANNOT BE PREPARED |
| BY AN AC CONTRACTOR. PROVIDE ENGINEERED DESIGN BY A FL. |
| LICENSED P.E., OR SUBMIT A FL. PRODUCT APPROVAL FOR TIE |
| DOWN CLIPS WITH APPROVAL STAMP BY THE DESIGN |
| PROFESSIONAL OF RECORD. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |
| 2ND REVIEW |
| |
| CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA |
| BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION |
| |
| 107.1 GENERAL: 107.2 CONSTRUCTION DOCUMENTS: 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS |
| |
| FLORIDA ENERGY CODE FBC 2014 |
| |
| (1) SYSTEM #5 ON THE APPROVED PLANS DOES NOT MATCH THE |
| HEAT LOAD CALCULATIONS DESIGN REQUIREMENTS. CHECK HEAT |
| LOAD CALCULATIONS AND MAKE ALL REQUIRED CORRECTIONS. |
| (2) FORM R405-2014 MUST BE COMPLETLY FILLED OUT WITH |
| ALL OF THE REQUIRED INFORMATION AND SIGNATURES. SEE |
| HIGHLIGHTED AREAS. ONE OF THE ENERGY CALCULATIONS IS |
| MISSING PAGE 1 OF 7. |
| (3) A CMC LICENSE CANNOT DESIGN CONDENSER TIE DOWNS. |
| CONDENSER TIE DOWNS MUST BE ENGINEERED. PROVIDE |
| ENGINEERED CONDENSER TIE DOWN DETAIL OR PROVIDE |
| ENGINEER STAMPED PLANS. (SEE PROVISIONAL ON PLANS) |
| |