Plan Review Notes
Plan Review Notes For Permit 16100893
Permit Number 16100893
Review Stop M
Sequence Number 2
Notes
Date Text
2017-02-15 18:09:422ND REVIEW
  
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 FLORIDA ENERGY CODE FBC 2014
  
 (1) SYSTEM #5 ON THE APPROVED PLANS DOES NOT MATCH THE
 HEAT LOAD CALCULATIONS DESIGN REQUIREMENTS. CHECK HEAT
 LOAD CALCULATIONS AND MAKE ALL REQUIRED CORRECTIONS.
 (2) FORM R405-2014 MUST BE COMPLETLY FILLED OUT WITH
 ALL OF THE REQUIRED INFORMATION AND SIGNATURES. SEE
 HIGHLIGHTED AREAS. ONE OF THE ENERGY CALCULATIONS IS
 MISSING PAGE 1 OF 7.
 (3) A CMC LICENSE CANNOT DESIGN CONDENSER TIE DOWNS.
 CONDENSER TIE DOWNS MUST BE ENGINEERED. PROVIDE
 ENGINEERED CONDENSER TIE DOWN DETAIL OR PROVIDE
 ENGINEER STAMPED PLANS. (SEE PROVISIONAL ON PLANS)
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER