Date |
Text |
2017-02-09 10:44:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THE PREVIOUS COMMENTS WERE NOT ADDRESSED. |
| |
| PREVIOUS COMMENYS: |
| |
| 1) PLEASE PROVIDE THE OCCUPANCY CLASSFICATION PER THE |
| FLORIDA FIRE PREVENTION CODE. |
| |
| ONE UNIT, # 5, HAS 6 BEDROOMS, A GAME ROOM, COMMON |
| WASHER/DRYER ROOM AND APPEARS TO HAVE A POSSIBLE USE |
| BEYOND A SINGLE FAMILY RESIDENCE. |
| |
| ADDITIONAL COMMENT: WILL THIS BUILDING BE USED AS A |
| RECOVERY TYPE RESIDENCE ? IF SO, HOW MANY RESIDENTS ARE |
| PROPOSED ? IT IS IMPERATIVE FOR THE LIFE SAFETY REVIEW |
| TO HAVE DEFINITIVE OCCUPANCY CLASSIFICATION. |
| |
| |
| |
| |
| 2) AS SUBMITTED THE CONSTRUCTION SHALL COMPLY WITH THE |
| FLORIDA FIRE PREVENTION CODE, NFPA 101, CHAPTER 30, NEW |
| APARTMENT BUILDINGS AND ALL APPLICABLE CODES. |
| |
| UNLESS OTHERWISE INDICATED SEPARATLY BY THE CORRECTION |
| OF # 1 ABOVE, PLEASE PROVIDE AN APPLICABLE NOTE, |
| |
| ADDITIONAL COMMENT: IF IT WILL NOT BE A RECOVERY |
| RESIDENCE AND IT IS NOT CONSIDERED A NEW APARTMENT, YOU |
| MUST INDICATE AND ENSURE COMPLIANCE WITH EXISTING |
| APARTMENT OCCUPANCCIES. |
| |
| |
| |
| 3) A FIRE SPRINKLER SYSTEM IS NOT INDICATED. PER NFPA |
| 101, CHAPTER 30: |
| |
| 30.3.5 EXTINGUISHMENT REQUIREMENTS. |
| 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| INSTALLED IN ACCORDANCE WITH 30.3.5.2. |
| 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| INSTALLED, EITHER FOR TOTAL OR PARTIAL BUILDING |
| COVERAGE, THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE |
| WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 AND |
| 30.3.5.4. IN BUILDINGS FOUR OR FEWER STORIES ABOVE |
| GRADE PLANE, SYSTEMS IN ACCORDANCE WITH NFPA 13R, |
| STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS IN |
| LOW-RISE RESIDENTIAL OCCUPANCIES, SHALL BE PERMITTED. |
| |
| PLEASE PROVIDE FIRE SPRINKLER DRAWINGS OR A NARRATIVE |
| IN COMPLIANCE WITH FS 61G - PER FLORIDA ADMINISTRATIVE |
| CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| |
| ADDITIONAL COMMENT: BASED ON THE OCCUPANCY |
| CLASSIFICATION AND OCCUPANCY USE A FIRE SPRINKLER |
| SYSTEM MAY STILL BE REQUIRED. PLEASE PROVIDE SPECIFIC |
| INFORMATION AND ANSWERS. |
| |
| |
| |
| |
| 4) A FIRE ALARM SYSTEM IN NOT INDICATED. PER NFPA 101, |
| CHAPTER 30 & CHAPTER 9. |
| |
| 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| INSTALLED IN ACCORDANCE WITH 30.3.5.2. |
| |
| 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| 9.6.1* GENERAL. |
| 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY |
| WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS |
| CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER |
| SYSTEM OR NEW FIRE ALARM SYSTEM IS REQUIRED BY THE |
| FLORIDA BUILDING CODE. |
| |
| |
| ADDITIONAL COMMENT: BASED ON THE OCCUPANCY |
| CLASSIFICATION AND OCCUPANCY USE A FIRE ALARM SYSTEM |
| MAY STILL BE REQUIRED. IF IT IS A EXISTING APARTMENT |
| OCCUPANCY CLASSIFICATION UNDER NFPA 101, CHAPTER 31, A |
| FIRE ALARM IS NOT REQUIRED. PLEASE PROVIDE SPECIFIC |
| INFORMATION AND ANSWERS. |
| |
| |
| |
| |
| 5) PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED |
| FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE |
| CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY |
| MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE |
| WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| WITH A MALTESE CROSS SIGN MEASURING 8 INCHES |
| HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED |
| REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED |
| WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. |
| A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| MARKED WITH THE LETTER "R". |
| B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| SHALL BE MARKED WITH THE LETTER "F". |
| C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| |
| ADDITIONAL COMMENT: COMMENT NOT ADDRESSED. |
| |
| |
| |
| 6) THE PROPOSED LAUNDRY ROOM SHALL BE PROTECTED BY 1 - |
| HOUR SEPARATION AND FIRE SPRINKLERS |
| |
| PER NFPA 101, CHAPTER 30, |
| |
| 30.3.2 PROTECTION FROM HAZARDS. |
| 30.3.2.1 HAZARDOUS AREAS. ANY HAZARDOUS AREA SHALL BE |
| PROTECTED IN ACCORDANCE WITH SECTION 8.7. |
| 30.3.2.1.1 THE AREAS DESCRIBED IN TABLE 30.3.2.1.1 |
| SHALL BE PROTECTED AS INDICATED. |
| |
| TABLE 30.3.2.1.1 LAUNDRIES 1 HOUR AND SPRINKLERS >100 |
| FT2 (>9.3 M2) OUTSIDE OF DWELLING UNITS |
| |
| ADDITIONAL COMMENT: THE SAME CODE IS APPLICABLE TO |
| EXISTING APARTMENTS. COMMENT NOT ADDRESSED. SECTION 8.7 |
| HAS SPECIFIC LANGUAGE THAT NEEDS TO BE USED IN THE |
| DESIGN OF THE LAUNDRY ROOM, NO WINDOWS, |
| 8.7 SPECIAL HAZARD PROTECTION. |
| 8.7.1 GENERAL. |
| 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF |
| HAZARD GREATER THAN THAT NORMAL TO THE GENERAL |
| OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE |
| PROVIDED BY ONE OF THE FOLLOWING MEANS: |
| (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT |
| WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN |
| ACCORDANCE WITH SECTION 8.3. |
| (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING |
| SYSTEMS IN ACCORDANCE WITH SECTION 9.7 |
| (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD |
| IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11 |
| THROUGH 43 |
| |
| 8.3 FIRE BARRIERS. |
| 8.3.1 GENERAL. |
| 8.3.1.1 FIRE BARRIERS USED TO PROVIDE ENCLOSURE, |
| SUBDIVISION, OR PROTECTION UNDER THIS CODE SHALL BE |
| CLASSIFIED IN ACCORDANCE WITH ONE OF THE FOLLOWING FIRE |
| RESISTANCE RATINGS: |
| (1) 3-HOUR FIRE RESISTANCE RATING |
| (2) 2-HOUR FIRE RESISTANCE RATING |
| (3) 1-HOUR FIRE RESISTANCE RATING |
| (4)* ?-HOUR FIRE RESISTANCE RATING |
| 8.3.1.2* FIRE BARRIERS SHALL COMPLY WITH ONE OF THE |
| FOLLOWING: |
| (1) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL |
| TO OUTSIDE WALL OR FROM ONE FIRE BARRIER TO ANOTHER, OR |
| A COMBINATION THEREOF, INCLUDING CONTINUITY THROUGH ALL |
| CONCEALED SPACES, SUCH AS THOSE FOUND ABOVE A CEILING, |
| INCLUDING INTERSTITIAL SPACES. |
| (2) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL |
| TO OUTSIDE WALL OR FROM ONE FIRE BARRIER TO ANOTHER, |
| AND FROM THE FLOOR TO THE BOTTOM OF THE INTERSTITIAL |
| SPACE, PROVIDED THAT THE CONSTRUCTION ASSEMBLY FORMING |
| THE BOTTOM OF THE INTERSTITIAL SPACE HAS A FIRE |
| RESISTANCE RATING NOT LESS THAN THAT OF THE FIRE |
| BARRIER. |
| |
| THE DOORS, O & P, TO THE LAUNDRY ARE NOTED TO HOLLOW |
| CORE, THERE ARE WINDOWS, AN EXIT STAIRWAY AND A WOOD |
| WALL ABOVE THE LAUNDRY. ON THE OTHER SIDE THERE IS A |
| WINDOW WITHIN 10 FT OF THE LAUNDRY THAT IS UNPROTECTED. |
| |
| PLEASE REVIEW, CLARIFY AND/OR CORRECT. |
| |
| |
| |
| 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| COMMENT REMAINS |
| |
| |
| 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| COMMENT REMAINS |
| |
| PETER LEDUC |
| FIRE MARSHAL |