2017-02-09 10:44:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE PREVIOUS COMMENTS WERE NOT ADDRESSED.
  
 PREVIOUS COMMENYS:
  
 1) PLEASE PROVIDE THE OCCUPANCY CLASSFICATION PER THE
 FLORIDA FIRE PREVENTION CODE.
  
 ONE UNIT, # 5, HAS 6 BEDROOMS, A GAME ROOM, COMMON
 WASHER/DRYER ROOM AND APPEARS TO HAVE A POSSIBLE USE
 BEYOND A SINGLE FAMILY RESIDENCE.
  
 ADDITIONAL COMMENT: WILL THIS BUILDING BE USED AS A
 RECOVERY TYPE RESIDENCE ? IF SO, HOW MANY RESIDENTS ARE
 PROPOSED ? IT IS IMPERATIVE FOR THE LIFE SAFETY REVIEW
 TO HAVE DEFINITIVE OCCUPANCY CLASSIFICATION.
  
  
  
  
 2) AS SUBMITTED THE CONSTRUCTION SHALL COMPLY WITH THE
 FLORIDA FIRE PREVENTION CODE, NFPA 101, CHAPTER 30, NEW
 APARTMENT BUILDINGS AND ALL APPLICABLE CODES.
  
 UNLESS OTHERWISE INDICATED SEPARATLY BY THE CORRECTION
 OF # 1 ABOVE, PLEASE PROVIDE AN APPLICABLE NOTE,
  
 ADDITIONAL COMMENT: IF IT WILL NOT BE A RECOVERY
 RESIDENCE AND IT IS NOT CONSIDERED A NEW APARTMENT, YOU
 MUST INDICATE AND ENSURE COMPLIANCE WITH EXISTING
 APARTMENT OCCUPANCCIES.
  
  
  
 3) A FIRE SPRINKLER SYSTEM IS NOT INDICATED. PER NFPA
 101, CHAPTER 30:
  
 30.3.5 EXTINGUISHMENT REQUIREMENTS.
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH 30.3.5.2.
 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS
 INSTALLED, EITHER FOR TOTAL OR PARTIAL BUILDING
 COVERAGE, THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE
 WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 AND
 30.3.5.4. IN BUILDINGS FOUR OR FEWER STORIES ABOVE
 GRADE PLANE, SYSTEMS IN ACCORDANCE WITH NFPA 13R,
 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS IN
 LOW-RISE RESIDENTIAL OCCUPANCIES, SHALL BE PERMITTED.
  
 PLEASE PROVIDE FIRE SPRINKLER DRAWINGS OR A NARRATIVE
 IN COMPLIANCE WITH FS 61G - PER FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 ADDITIONAL COMMENT: BASED ON THE OCCUPANCY
 CLASSIFICATION AND OCCUPANCY USE A FIRE SPRINKLER
 SYSTEM MAY STILL BE REQUIRED. PLEASE PROVIDE SPECIFIC
 INFORMATION AND ANSWERS.
  
  
  
  
 4) A FIRE ALARM SYSTEM IN NOT INDICATED. PER NFPA 101,
 CHAPTER 30 & CHAPTER 9.
  
 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY
 AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 INSTALLED IN ACCORDANCE WITH 30.3.5.2.
  
 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 9.6.1* GENERAL.
 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY
 WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS
 CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER
 SYSTEM OR NEW FIRE ALARM SYSTEM IS REQUIRED BY THE
 FLORIDA BUILDING CODE.
  
  
 ADDITIONAL COMMENT: BASED ON THE OCCUPANCY
 CLASSIFICATION AND OCCUPANCY USE A FIRE ALARM SYSTEM
 MAY STILL BE REQUIRED. IF IT IS A EXISTING APARTMENT
 OCCUPANCY CLASSIFICATION UNDER NFPA 101, CHAPTER 31, A
 FIRE ALARM IS NOT REQUIRED. PLEASE PROVIDE SPECIFIC
 INFORMATION AND ANSWERS.
  
  
  
  
 5) PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED
 FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 ADDITIONAL COMMENT: COMMENT NOT ADDRESSED.
  
  
  
 6) THE PROPOSED LAUNDRY ROOM SHALL BE PROTECTED BY 1 -
 HOUR SEPARATION AND FIRE SPRINKLERS
  
 PER NFPA 101, CHAPTER 30,
  
 30.3.2 PROTECTION FROM HAZARDS.
 30.3.2.1 HAZARDOUS AREAS. ANY HAZARDOUS AREA SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 8.7.
 30.3.2.1.1 THE AREAS DESCRIBED IN TABLE 30.3.2.1.1
 SHALL BE PROTECTED AS INDICATED.
  
 TABLE 30.3.2.1.1 LAUNDRIES 1 HOUR AND SPRINKLERS >100
 FT2 (>9.3 M2) OUTSIDE OF DWELLING UNITS
  
 ADDITIONAL COMMENT: THE SAME CODE IS APPLICABLE TO
 EXISTING APARTMENTS. COMMENT NOT ADDRESSED. SECTION 8.7
 HAS SPECIFIC LANGUAGE THAT NEEDS TO BE USED IN THE
 DESIGN OF THE LAUNDRY ROOM, NO WINDOWS,
 8.7 SPECIAL HAZARD PROTECTION.
 8.7.1 GENERAL.
 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF
 HAZARD GREATER THAN THAT NORMAL TO THE GENERAL
 OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE
 PROVIDED BY ONE OF THE FOLLOWING MEANS:
 (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT
 WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE WITH SECTION 8.3.
 (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING
 SYSTEMS IN ACCORDANCE WITH SECTION 9.7
 (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD
 IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11
 THROUGH 43
  
 8.3 FIRE BARRIERS.
 8.3.1 GENERAL.
 8.3.1.1 FIRE BARRIERS USED TO PROVIDE ENCLOSURE,
 SUBDIVISION, OR PROTECTION UNDER THIS CODE SHALL BE
 CLASSIFIED IN ACCORDANCE WITH ONE OF THE FOLLOWING FIRE
 RESISTANCE RATINGS:
 (1) 3-HOUR FIRE RESISTANCE RATING
 (2) 2-HOUR FIRE RESISTANCE RATING
 (3) 1-HOUR FIRE RESISTANCE RATING
 (4)* ?-HOUR FIRE RESISTANCE RATING
 8.3.1.2* FIRE BARRIERS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 (1) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL
 TO OUTSIDE WALL OR FROM ONE FIRE BARRIER TO ANOTHER, OR
 A COMBINATION THEREOF, INCLUDING CONTINUITY THROUGH ALL
 CONCEALED SPACES, SUCH AS THOSE FOUND ABOVE A CEILING,
 INCLUDING INTERSTITIAL SPACES.
 (2) THE FIRE BARRIERS ARE CONTINUOUS FROM OUTSIDE WALL
 TO OUTSIDE WALL OR FROM ONE FIRE BARRIER TO ANOTHER,
 AND FROM THE FLOOR TO THE BOTTOM OF THE INTERSTITIAL
 SPACE, PROVIDED THAT THE CONSTRUCTION ASSEMBLY FORMING
 THE BOTTOM OF THE INTERSTITIAL SPACE HAS A FIRE
 RESISTANCE RATING NOT LESS THAN THAT OF THE FIRE
 BARRIER.
  
 THE DOORS, O & P, TO THE LAUNDRY ARE NOTED TO HOLLOW
 CORE, THERE ARE WINDOWS, AN EXIT STAIRWAY AND A WOOD
 WALL ABOVE THE LAUNDRY. ON THE OTHER SIDE THERE IS A
 WINDOW WITHIN 10 FT OF THE LAUNDRY THAT IS UNPROTECTED.
  
 PLEASE REVIEW, CLARIFY AND/OR CORRECT.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 COMMENT REMAINS
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 COMMENT REMAINS
  
 PETER LEDUC
 FIRE MARSHAL