2016-12-08 17:58:20CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE PROPER VENTILATION FOR LIVING AREAS IN
 LIVING UNITS #1, #2, #3.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (2) PROVIDE HEAT LOAD CALCULATIONS AS PER R403.6.1 (SEE
 BELOW)
  
 R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED
 IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN
 SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER
 SAFETY FACTORS, PROVISIONS FOR FUTURE EXPANSION OR
 OTHER FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM
 SIZING CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY
 LOCAL INTERMITTENT MECHANICAL VENTILATION SUCH AS
 STANDARD KITCHEN AND BATHROOM EXHAUST SYSTEMS.
  
 (3) PROVIDE FORM R405-2014 ENERGY CALCULATIONS. (SEE
 BELOW)
  
 FLORIDA ENERGY CODE - SECTION R202 RENOVATED BUILDINGS
 - A RESIDENTIAL OR NONRESIDENTIAL BUILDING UNDERGOING
 ALTERATION THAT VARIES INSULATION, HVAC SYSTEMS, WATER
 HEATING SYSTEMS, OR EXTERIOR ENVELOPE CONDITIONS,
 PROVIDED THE ESTIMATED COST OF RENOVATION EXCEEDS 30
 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE.
  
 C101.4.4 CHANGE IN OCCUPANCY OR USE.
 SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD
 RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL
 OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE
 THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE
 C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1)
 OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY
 WITH SECTION C405.5.
  
 R101.4.3 ADDITIONS, ALTERATIONS, RENOVATIONS OR
 REPAIRS.
 ADDITIONS, ALTERATIONS, RENOVATIONS OR REPAIRS TO AN
 EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF
 SHALL CONFORM TO THE PROVISIONS OF THIS CODE AS THEY
 RELATE TO NEW CONSTRUCTION WITHOUT REQUIRING THE
 UNALTERED PORTION(S) OF THE EXISTING BUILDING OR
 BUILDING SYSTEM TO COMPLY WITH THIS CODE. ADDITIONS,
 ALTERATIONS, RENOVATIONS OR REPAIRS SHALL NOT CREATE AN
 UNSAFE OR HAZARDOUS CONDITION OR OVERLOAD EXISTING
 BUILDING SYSTEMS. AN ADDITION SHALL BE DEEMED TO COMPLY
 WITH THIS CODE IF THE ADDITION ALONE COMPLIES OR IF THE
 EXISTING BUILDING AND ADDITION COMPLY WITH THIS CODE AS
 A SINGLE BUILDING.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  