2016-11-04 16:52:54 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) PLEASE PROVIDE THE OCCUPANCY CLASSFICATION PER THE |
| FLORIDA FIRE PREVENTION CODE. |
| |
| ONE UNIT, # 5, HAS 6 BEDROOMS, A GAME ROOM, COMMON |
| WASHER/DRYER ROOM AND APPEARS TO HAVE A POSSIBLE USE |
| BEYOND A SINGLE FAMILY RESIDENCE. |
| |
| |
| 2) AS SUBMITTED THE CONSTRUCTION SHALL COMPLY WITH THE |
| FLORIDA FIRE PREVENTION CODE, NFPA 101, CHAPTER 30, NEW |
| APARTMENT BUILDINGS AND ALL APPLICABLE CODES. |
| |
| UNLESS OTHERWISE INDICATED SEPARATLY BY THE CORRECTION |
| OF # 1 ABOVE, PLEASE PROVIDE AN APPLICABLE NOTE, |
| |
| |
| 3) A FIRE SPRINKLER SYSTEM IS NOT INDICATED. PER NFPA |
| 101, CHAPTER 30: |
| |
| 30.3.5 EXTINGUISHMENT REQUIREMENTS. |
| 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| INSTALLED IN ACCORDANCE WITH 30.3.5.2. |
| 30.3.5.2 WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| INSTALLED, EITHER FOR TOTAL OR PARTIAL BUILDING |
| COVERAGE, THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE |
| WITH SECTION 9.7, AS MODIFIED BY 30.3.5.3 AND |
| 30.3.5.4. IN BUILDINGS FOUR OR FEWER STORIES ABOVE |
| GRADE PLANE, SYSTEMS IN ACCORDANCE WITH NFPA 13R, |
| STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS IN |
| LOW-RISE RESIDENTIAL OCCUPANCIES, SHALL BE PERMITTED. |
| |
| PLEASE PROVIDE FIRE SPRINKLER DRAWINGS OR A NARRATIVE |
| IN COMPLIANCE WITH FS 61G - PER FLORIDA ADMINISTRATIVE |
| CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING |
| DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE |
| WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS |
| APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD |
| OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM |
| TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP |
| DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED |
| INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS. |
| |
| |
| |
| 4) A FIRE ALARM SYSTEM IN NOT INDICATED. PER NFPA 101, |
| CHAPTER 30 & CHAPTER 9. |
| |
| 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| INSTALLED IN ACCORDANCE WITH 30.3.5.2. |
| |
| 9.6 FIRE DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| 9.6.1* GENERAL. |
| 9.6.1.1 THE PROVISIONS OF SECTION 9.6 SHALL APPLY ONLY |
| WHERE SPECIFICALLY REQUIRED BY ANOTHER SECTION OF THIS |
| CODE OR WHERE SUPERVISION OF A NEW FIRE SPRINKLER |
| SYSTEM OR NEW FIRE ALARM SYSTEM IS REQUIRED BY THE |
| FLORIDA BUILDING CODE. |
| |
| |
| |
| 5) PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED |
| FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE |
| CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY |
| MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE |
| WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME |
| TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED |
| WITH A MALTESE CROSS SIGN MEASURING 8 INCHES |
| HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED |
| REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED |
| WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. |
| A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| MARKED WITH THE LETTER "R". |
| B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| SHALL BE MARKED WITH THE LETTER "F". |
| C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| |
| |
| |
| 6) THE PROPOSED LAUNDRY ROOM SHALL BE PROTECTED BY 1 - |
| HOUR SEPARATION AND FIRE SPRINKLERS |
| |
| PER NFPA 101, CHAPTER 30, |
| |
| 30.3.2 PROTECTION FROM HAZARDS. |
| 30.3.2.1 HAZARDOUS AREAS. ANY HAZARDOUS AREA SHALL BE |
| PROTECTED IN ACCORDANCE WITH SECTION 8.7. |
| 30.3.2.1.1 THE AREAS DESCRIBED IN TABLE 30.3.2.1.1 |
| SHALL BE PROTECTED AS INDICATED. |
| |
| TABLE 30.3.2.1.1 LAUNDRIES 1 HOUR AND SPRINKLERS >100 |
| FT2 (>9.3 M2) OUTSIDE OF DWELLING UNITS |
| |
| |
| 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |