  ELECTRICAL PLAN REVIEW COMMENTS
  
 - THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] THE APPLICABLE CODES IN EFFECT ARE NEC 2011, NFPA 72
 (2010), NFPA 101 (2012). PLEASE CORRECT NOTE 1
 ACCORDINGLY.
  
 2] SHOW CIRCUIT DESIGNATION # ON THE FLOOR PLAN TO
 MATCH PANEL SCHEDULE. FBC-107
  
 3] SHOW ALL PANELBOARDS LOCATION ON THE FLOOR PLAN TO
 VERIFY WORK SPACE CLEARANCES. NEC 110.26
  
 4] AT LEAST 1 WALL SWITCHED CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED TO PROVIDE ILLUMINATION ON THE
 EXTERIOR SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE
 LEVEL ACCESS PER NEC 210.70(A)(2).
  
 5] ADD GFI SYMBOL TO RECEPTACLE BY THE RANGE IN THE
 KITCHEN COUNTER-TOP (RED-LINED ON PLANS), ALSO ADD GFI
 "WP/WR" SYMBOL TO RECEPTACLE OUTLETS INSTALLED
 OUTDOORS. NEC 210.8(A)(6), 210.8(A)(3) &, 406.9(B).
  
 6] ALL AREAS SPECIFIED IN NEC 210.52 SHALL HAVE AFCI
 PROTECTION PER NEC 210.12(A). CORRECT ELECTRICAL NOTE
 22.
  
 7] ADD GENERAL ELECTRICAL NOTE FOR TAMPER RESISTANT
 RECEPTACLES IN ACCORDANCE WITH NEC 406.12.
  
 8] ALL MEANS OF EGRESS STAIRWAYS IN COMMON AREAS WILL
 REQUIRE EXIT LIGHTS & EMERGENCY LIGHTS THROUGH-OUT THE
 EXIT DISCHARGE. EXTERIOR ILLUMINATION IS REQUIRED TO
 ILLUMINATE EGRESS PATH UNTIL PUBLIC WAY IS SAFELY
 REACHED. FBC 1011 & 1006 (SHOW COMPLIANCE).
  
 9] EXIT & EMERGENCY LIGHTS SHALL BE FED AHEAD OF LOCAL
 LIGHTING AREA SERVED. NEC 700.12(F)(4)
  
 10] FIRE MARSHALL SHALL DETERMINE IF A FIRE ALARM IS
 REQUIRED OR IF SINGLE STATION SMOKE ALARMS WILL SUFFICE
 ENOUGH FIRE PROTECTION.
  
 11] EACH OCCUPANT SHALL HAVE READY ACCESS TO ALL
 OVERCURRENT DEVICES, AS CONFIGURED ACCESSIBILITY IS
 LIMITED. PLEASE SEE NEC 240.24(B)
  
 12] PROVIDE AIC CALCULATIONS TO VERIFY SHORT-CIRCUIT
 RATINGS OF ELECTRICAL EQUIPMENT. NEC 110.10 & 110.9
  
 13] CLARIFY RISER DIAGRAM FEEDER LAYOUT, EACH UNIT THAT
 WILL BE INDIVIDUALLY METERED SHALL HAVE ITS DEDICATED
 PANEL BOARD WITH ALL ASSOCIATED LOADS TERMINATING
 ACCORDINGLY. ELIMINATE PANELS "C1", "C2", "C3" TO
 COMPLY WITH NEC REQUIREMENTS & SHOW PANEL SCHEDULES
 WITH MATCHING FLOOR PLAN CIRCUITS. ADJUST RISER-DIAGRAM
 DETAIL TO REFLECT ALL CONDUIT & WIRE SIZES. FBC
 107.3.5.3
  
 - PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON?T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER