2016-11-01 09:43:11 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THE PROPOSED PROJECT INDICATES MULTIPLE NEW FIRE |
| ALARM DEVICES THAT WERE NOT EXISTING REPLACEMENTS. |
| |
| PLEASE PROVIDE REVISED VOLTAGE DROP AND BATTERY |
| CALCULATIONS TO INCLUDE ALL NEW DEVICES. |
| |
| |
| |
| 2) THERE WERE NO PRODUCTS SPECS OR SHEETS PROVIDED. |
| |
| PLEASE PROVIDE ALL APPLICABLE PRODUCTS SHEETS FOR ALL |
| NEW DEVICES. |
| |
| |
| |
| 3) THE NEW DEVICES ARE NOT SHOWN ON SYSTEM DIAGRAM. |
| |
| PLEASE PROVIDE A SYSTEM DIAGRAM INCLUDING ADDRESSABLE |
| LABELS. |
| |
| |
| |
| 4) THERE WERE NO WIRING DIAGRAMS PROVIDED. |
| |
| PLEASE PROVIDE NEW WIRING DIAGRAMS FOR ALL NEW DEVICES |
| AND/OR ANY NEW WIRING INSTALLATIONS. |
| |
| |
| |
| 5) THERE IS NO INDICATIONS THAT THE EXISTING FIRE ALARM |
| WILL REMAIN FULLY FUNCTIONAL DURING CONSTRUCTION |
| PERIOD. |
| |
| PER NFPA NFPA 101, CHAPTER 9, BUILDING SERVICE AND FIRE |
| PROTECTION EQUIPMENT |
| |
| 9.6.1.6* WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF |
| SERVICE FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE |
| AUTHORITY HAVING JURISDICTION SHALL BE NOTIFIED, AND |
| THE BUILDING SHALL BE EVACUATED, OR AN APPROVED FIRE |
| WATCH SHALL BE PROVIDED FOR ALL PARTIES LEFT |
| UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE ALARM SYSTEM |
| HAS BEEN RETURNED TO SERVICE. |
| |
| PLEASE PROVIDE A NOTE OF COMPLIANCE. |
| |
| |
| |
| 6) A NFPA 72 INSPECTION AND FULL FIRE ALARM TEST SHALL |
| BE REQUIRED FOR THIS PROPOSED INSTALLATION. |
| |
| |
| |
| 7) PLEASE PROVIDE PLAN SHEET REVISION CLOUDS OR |
| NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| |
| |
| 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |
| |
| |