Plan Review Notes For Permit 16100856 |
Permit Number |
16100856 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-01 16:51:33 | RESIDENTIAL (R3) BUILDING REVISION CHECKLIST. | | CODE: FBC 5TH EDITION (2014). | | | | ORIGINAL COMMENT REQUIRED ON PROVISO DATED 07/08/16: | | 1- PROVIDE COMPLETE DETAILS/SPECIFICATIONS SHOWING HOW | | COMPLYING WITH THE ADDITION ROOF VENTILATION SEC. R806 | | FBC-RESIDENTIAL, 5TH EDITION (2014). | | | | RESPONSE: | | GENERAL NOTE ON SHEET A-102 REQUIRING 600 SQ. INCHES IS | | NOT ENOUGH INFORMATION. PROFESSIONAL DESIGNER OF RECORD | | TO SPECIFY ON PLANS VENT SIZES AND LOCATION SHOWING | | COMPLIANCE WITH SEC. R806 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|