2016-11-01 16:51:33RESIDENTIAL (R3) BUILDING REVISION CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT REQUIRED ON PROVISO DATED 07/08/16:
 1- PROVIDE COMPLETE DETAILS/SPECIFICATIONS SHOWING HOW
 COMPLYING WITH THE ADDITION ROOF VENTILATION SEC. R806
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 RESPONSE:
 GENERAL NOTE ON SHEET A-102 REQUIRING 600 SQ. INCHES IS
 NOT ENOUGH INFORMATION. PROFESSIONAL DESIGNER OF RECORD
 TO SPECIFY ON PLANS VENT SIZES AND LOCATION SHOWING
 COMPLIANCE WITH SEC. R806 FBC-RESIDENTIAL.
  
  