Plan Review Notes
Plan Review Notes For Permit 16100844
Permit Number 16100844
Review Stop E
Sequence Number 1
Notes
Date Text
2016-10-31 11:52:49INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE SHOW JACUZZI TO BE PROTECTED BY GFCI BREAKER
 TO BE READILY ACCESSIBLE. A NOTE WILL SUFFICE.
 2. PROVIDE A NOTE TO INDICATE REQUIRED TAMPER RESISTANT
 RECEPTACLE. FBC RES E4002.14
 3. PROVIDE A NOTE TO PROVIDE AFCI PROTECTION PER FBC
 RES E3902.12
 4. PROVIDE THE EXISTING PANEL SCHEDULE REFLECTING NEW
 JACUZZI AND WATER VALVE LOADS. FBC 107.3.5
 5. CLARIFY IF THERE ARE EXISTING SMOKE DETECTORS IN
 UNIT IF NOT SHOW AND PROVIDE ON DRAWINGS. FBC RES 315
 6. PROVIDE SPEC SHEETS FOR THE NEW 120V ELECTRONIC
 SHOWER CONTROL VALVE.
 7. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  