Plan Review Notes
Plan Review Notes For Permit 16100840
Permit Number 16100840
Review Stop M
Sequence Number 1
Notes
Date Text
2016-11-04 15:53:321ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100840
 11/4/16
  
 1) THE SUBMITTED AC PLAN HAS BEEN DISAPPROVED FOR THE
 FOLLOWING DEFICIENCIES:
  
 A) AIR CONDITIONING SYSTEMS MAY BE DESIGNED BY AN
 INSTALLING AIR-CONDITIONING CONTRACTOR OR A FL.
 LICENSED ENGINEER. PALM BEACH BUILDING CO, WHOSE NAME
 APPEARS ON THE PLAN, IS NEITHER THE CONTRACTOR OR
 ENGINEER OF RECORD- SECTION 105.3.1.2 FBC-14 BUILDING.
  
 B) ALL PLANS SUBMITTED FOR REVIEW MUST BEAR THE
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN-
 SECTION 107.2.1 WPB AMENMENTS TO THE FBC.
  
 C) THE PLAN DOES NOT PROVIDE THE BASIC FLOOR PLAN
 LAYOUT OF THE HOUSE WITH ALL ROOMS AND SPACES SHOWN AND
 IDENTIFIED, AND THE PRINT INDICATING THE SUPPLY CFMS AT
 EACH DIFFUSER IS ILLEGIBLE- SECTION 107.2.1.
  
 D) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN AND
 CLEARLY SHOW THE LOCATIONS OF THE AIR HANDLER AND
 CONDENSER.
  
 E) INDICATE HOW AIR WILL BE RETURNED FORM THE BEDROOMS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER