Plan Review Notes For Permit 16100840 |
Permit Number |
16100840 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-04 15:53:32 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16100840 | | 11/4/16 | | | | 1) THE SUBMITTED AC PLAN HAS BEEN DISAPPROVED FOR THE | | FOLLOWING DEFICIENCIES: | | | | A) AIR CONDITIONING SYSTEMS MAY BE DESIGNED BY AN | | INSTALLING AIR-CONDITIONING CONTRACTOR OR A FL. | | LICENSED ENGINEER. PALM BEACH BUILDING CO, WHOSE NAME | | APPEARS ON THE PLAN, IS NEITHER THE CONTRACTOR OR | | ENGINEER OF RECORD- SECTION 105.3.1.2 FBC-14 BUILDING. | | | | B) ALL PLANS SUBMITTED FOR REVIEW MUST BEAR THE | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN- | | SECTION 107.2.1 WPB AMENMENTS TO THE FBC. | | | | C) THE PLAN DOES NOT PROVIDE THE BASIC FLOOR PLAN | | LAYOUT OF THE HOUSE WITH ALL ROOMS AND SPACES SHOWN AND | | IDENTIFIED, AND THE PRINT INDICATING THE SUPPLY CFMS AT | | EACH DIFFUSER IS ILLEGIBLE- SECTION 107.2.1. | | | | D) PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN AND | | CLEARLY SHOW THE LOCATIONS OF THE AIR HANDLER AND | | CONDENSER. | | | | E) INDICATE HOW AIR WILL BE RETURNED FORM THE BEDROOMS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|