Plan Review Notes
Plan Review Notes For Permit 16100831
Permit Number 16100831
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-10-27 15:01:38THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) TEST AT WORKING PRESSURE FOR 2 HRS PER NFPA 13.
  
 24.2.1.6 MODIFICATIONS THAT CANNOT BE ISOLATED, SUCH AS
 RELOCATED DROPS, SHALL NOT REQUIRE TESTING IN EXCESS OF
 SYSTEM WORKING PRESSURE.
  
 24.2.1.7 LOSS SHALL BE DETERMINED BY A DROP IN GAUGE
 PRESSURE OR VISUAL LEAKAGE.
  
 24.2.1.8* THE TEST PRESSURE SHALL BE READ FROM A GAUGE
 LOCATED AT THE LOW ELEVATION POINT OF THE SYSTEM OR
 PORTION BEING TESTED. THE PRESSURES IN PIPING AT HIGHER
 ELEVATIONS SHALL BE PERMITTED TO BE LESS THAN 200 PSI
 (13.8 BAR) WHEN ACCOUNTING FOR ELEVATION LOSSES.
 SYSTEMS OR PORTIONS OF SYSTEMS THAT CAN BE ISOLATED
 SHALL BE PERMITTED TO BE TESTED SEPARATELY.
  
 A.24.2.1.8 AS AN EXAMPLE, IN A SYSTEM THAT HAD PIPING
 AT AN ELEVATION THAT WAS 25 FT (7.6 M) HIGHER THAN THE
 TEST GAUGE, AN ACCEPTABLE PRESSURE DURING THE
 HYDROSTATIC TEST IS 189 PSI (13.03 BAR) AT THE TOP OF
 THE SYSTEM DUE TO THE LOSS OF 11 PSI (0.76 BAR) IN
 ELEVATION PRESSURE [25 FT ? 0.433 PSI/FT = 11 PSI (0.76
 BAR)].
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  