Plan Review Notes For Permit 16100758 |
Permit Number |
16100758 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2017-01-23 10:31:21 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | | | 1) FIRE HYDRANT AND FIRE LAINE SHALL BE INSTALLED PER | | NFPA 24, STANDARD FOR THE INSTALLATION OF PRIVATE FIRE | | SERVICE MAINS AND THEIR APPURTENANCES, 2010 EDITION. | | | | | | 2) ALL UNDERGROUND WORK SHALL BE INSPECTOR BY A FIRE | | INSPECTOR PRIOR TO COVER OVER. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|