Plan Review Notes
Plan Review Notes For Permit 16100758
Permit Number 16100758
Review Stop B
Sequence Number 1
Notes
Date Text
2016-11-01 17:27:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE SITE PLAN TO SHOW PROPOSED LOCATION OF
 CONSTRUCTION TRAILER AND REQUIRED RAMP AND STAIRS, FBC
 107.
  
 2. ALTHOUGH EXEMPT FROM FLORIDA BUILDING CODE PER
 FLORIDA STATUTE, THIS DOES NOT APPEAR TO BE EXEMPT FROM
 ACCESSIBILITY. A RAMP IS REQUIRED. THIS MAY BE A
 PROVISO ITEM UPON REQUEST. IF APPLICANT FEELS THEY ARE
 EXEMPT FROM ACCESSIBILITY, PLEASE CONTACT ME TO
 DISCUSS. FBC 5TH EDITION ACCESSIBILITY 402.
  
 3. ALTHOUGH EXEMPT FROM FLORIDA BUILDING CODE PER
 FLORIDA STATUTE, THIS STRUCTURE IS NOT EXEMPT FROM NFIP
 (AKA FEMA) REQUIREMENTS. CLARIFY THE HEIGHT OF THE
 FOUNDATION FOR THIS STRUCTURE. IF THE FOUNDATION WILL
 BE SUBJECT TO FLOOD LOADS (INSTALLED BELOW 14 FT), THE
 FOUNDATION IS TO BE DESIGNED TO RESIST FLOOD LOADS FBC
 1622, CITY OF WEST PALM BEACH MUNICIPAL CODE 94-546.
 THERE IS A NOTE ON THE PLAN WHICH STATES THAT THIS
 CANNOT BE SUBJECT TO WAVE ACTION, BUT DOES NOT STATE
 THAT IT WILL RESIST FLOOD LOADS. CLARIFICATION IS
 NEEDED. A LETTER FROM THE ENGINEER WILL SUFFICE.
  
 4. SEE NFIP REVIEW.
  
  
  
  
  
  