Plan Review Notes For Permit 16100758 |
Permit Number |
16100758 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-01 17:27:25 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. REVISE SITE PLAN TO SHOW PROPOSED LOCATION OF | | CONSTRUCTION TRAILER AND REQUIRED RAMP AND STAIRS, FBC | | 107. | | | | 2. ALTHOUGH EXEMPT FROM FLORIDA BUILDING CODE PER | | FLORIDA STATUTE, THIS DOES NOT APPEAR TO BE EXEMPT FROM | | ACCESSIBILITY. A RAMP IS REQUIRED. THIS MAY BE A | | PROVISO ITEM UPON REQUEST. IF APPLICANT FEELS THEY ARE | | EXEMPT FROM ACCESSIBILITY, PLEASE CONTACT ME TO | | DISCUSS. FBC 5TH EDITION ACCESSIBILITY 402. | | | | 3. ALTHOUGH EXEMPT FROM FLORIDA BUILDING CODE PER | | FLORIDA STATUTE, THIS STRUCTURE IS NOT EXEMPT FROM NFIP | | (AKA FEMA) REQUIREMENTS. CLARIFY THE HEIGHT OF THE | | FOUNDATION FOR THIS STRUCTURE. IF THE FOUNDATION WILL | | BE SUBJECT TO FLOOD LOADS (INSTALLED BELOW 14 FT), THE | | FOUNDATION IS TO BE DESIGNED TO RESIST FLOOD LOADS FBC | | 1622, CITY OF WEST PALM BEACH MUNICIPAL CODE 94-546. | | THERE IS A NOTE ON THE PLAN WHICH STATES THAT THIS | | CANNOT BE SUBJECT TO WAVE ACTION, BUT DOES NOT STATE | | THAT IT WILL RESIST FLOOD LOADS. CLARIFICATION IS | | NEEDED. A LETTER FROM THE ENGINEER WILL SUFFICE. | | | | 4. SEE NFIP REVIEW. | | | | | | | | | | | | |
|