Plan Review Notes For Permit 16100755 |
Permit Number |
16100755 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-19 05:34:35 | 1) A SERVICE SINK AND DRINKING FOUNTAIN ARE REQUIRED IN | | THIS SPACE PER THE 2014 FPC TABLE 403.1 IF THEY ARE NOT | | PROVIDED IN THE COMMON AREA. IF THEY ARE LOCATED IN THE | | COMMON AREA, SUBMIT A PLAN THAT SHOWS THE LOCATION OF | | THE FIXTURES. AMINIMUM OF 2 DRINKING FOUNTAINS SHALL BE | | PROVIDED. FPC TABLE 403.1 FOOTNOTE # F & FAC SEC.211.2. | | 2) AIR ARRESTORS ARE REQUIRED ON THE DISHWASHER WATER | | SUPPLY PER 2014 FPC SEC.604.9. | | 3) BACKFLOW PREVENTERS ARE REQUIRED ON THE WATER LINE | | TO THE REFRIGERATOR & COFFE MAKER. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|