2016-10-31 09:37:501ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16100755
 10/31/16
  
 1) PROVIDE SIZING CALCULATIONS FOR THE NEW AHU'S 1 & 2-
 SECTION 403.2.1 FBC-14 ENERGY CONSERVATION.
  
 2) THE O/A TO ALL UNITS REQUIRES AUTOMATIC CONTROL AS
 OUTLINED IN SECTION C403.2.4.4.
  