Plan Review Notes For Permit 16100755 |
Permit Number |
16100755 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-10-31 09:37:50 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, | | ENERGY CONSERVATION CODES | | PERMIT #16100755 | | 10/31/16 | | | | 1) PROVIDE SIZING CALCULATIONS FOR THE NEW AHU'S 1 & 2- | | SECTION 403.2.1 FBC-14 ENERGY CONSERVATION. | | | | 2) THE O/A TO ALL UNITS REQUIRES AUTOMATIC CONTROL AS | | OUTLINED IN SECTION C403.2.4.4. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|