Plan Review Notes
Plan Review Notes For Permit 16100738
Permit Number 16100738
Review Stop E
Sequence Number 1
Notes
Date Text
2016-11-02 09:48:191ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - THE PLANS SUBMMITTED DON'T CONTAIN ANY ELECTRICAL
 DETAILS, THE ONLY ELECTRICAL INFORMATION IS A NOTE FOR
 AN EXISTING 20 AMP DISCONNECT WHICH COMPLIES WITH NEC
 600.6. BELOW FIND A LIST OF ITEMS REQUIRED.
  
 1] PROVIDE A ELECTRICAL PLAN TO INCLUDE MINIMUM A 20
 AMP DEDICATED CIRCUIT FOR THE SIGN PER NEC 600.5
  
 2] ADD A BLOCK NOTE FOR ALL GROUNDING AND BONDING TO
 COMPLY WITH NEC 600.7
  
 3] LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. FBC-E
 SECTION C405.2.4 EXTERIOR LIGHTING CONTROLS (SHOW
 COMPLIANCE)
  
 4] THE PERMIT VALUATION AND PERMIT FEE MUST
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. PLEASE INCREASE THE VALUATION
 ACCORDINGLY AND SHOW PROOF WITH AN OWNER SIGNED
 CONTRACT. FBC- 109.3
  
  