Review Stop E
Sequence Number 1
Notes
Date Text
2016-11-03 11:15:561ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] PLEASE CLARIFY THE ELECTRICAL SCOPE OF WORK. IF
 RUNING NEW CICUITS SHOW A SMALL ONE LINE DIAGRAM
 REFLECTING CONDUCTOR AND RACEWAY ROUTING PLUS A PANEL
 SCHEDULE IDENTIFYING CIRCUIT # WITH OVERCURRENT
 PROTECTION AMPERE RATING.
  
 2] PROVIDE MANUFACTURE SPECIFICATIONS INDICATING
 NAMEPLATE RATING OF EQUIPMENT IDENTIFYING MINIMUM
 AMPERE RATING AND MAXIMUM OVERCURRENT DEVICE PER NEC
 440.