Plan Review Notes For Permit 16100716 |
Permit Number |
16100716 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-10-26 15:08:11 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16100716 | | 10/25/16 | | | | 1) PROVIDE AN AHRI CERTIFICATE FOR THE REVISED GOODMAN | | SYSTEM. | | | | 2) THE 8" ROUND DUCT SUPPLYING 303 CFM'S IN THE DINING | | ROOM IS UNDERSIZED PER THE MANUAL J CALCULATIONS | | SUBMITTED UNDER THE MASTER PERMIT #15120534- MINIMUM 9" | | DUCT REQUIRED. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|