Plan Review Notes For Permit 16100588 |
Permit Number |
16100588 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-02 14:55:22 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16100588 | | 11/2/16 | | | | 1) SHEET M2.1: CORRIDORS SHALL NOT BE USED TO CONVEY | | RETURN AIR- SECTION 601.2. DUCTED RETURNS ARE REQUIRED | | FROM THE TRAINING AND SERVER ROOMS. | | | | 2) M2.1: PROVIDE THE FLEX DUCT SIZES ON THE PLAN. | | | | 3) PROVIDE ENGINEERING FOR INSTALLATION OF THE NEW | | 2-TON RTU-6- SEE SECTION 301.15. CLARIFY IF A NEW CURB | | OR CURB ADAPTER IS BEING INSTALLED, AND PROVIDE THE | | WIND LOAD DESIGN CRITERIA ON THE PLAN AS OUTLINED IN | | SECTION 1609 FBC-14 BUILDING. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|