2016-11-02 14:55:221ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100588
 11/2/16
  
 1) SHEET M2.1: CORRIDORS SHALL NOT BE USED TO CONVEY
 RETURN AIR- SECTION 601.2. DUCTED RETURNS ARE REQUIRED
 FROM THE TRAINING AND SERVER ROOMS.
  
 2) M2.1: PROVIDE THE FLEX DUCT SIZES ON THE PLAN.
  
 3) PROVIDE ENGINEERING FOR INSTALLATION OF THE NEW
 2-TON RTU-6- SEE SECTION 301.15. CLARIFY IF A NEW CURB
 OR CURB ADAPTER IS BEING INSTALLED, AND PROVIDE THE
 WIND LOAD DESIGN CRITERIA ON THE PLAN AS OUTLINED IN
 SECTION 1609 FBC-14 BUILDING.
  