Plan Review Notes For Permit 16100586 |
Permit Number |
16100586 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-10-22 04:59:06 | 1) CLEARLY SHOW THE SCOPE OF WORK ON THE SUBMITTED | | PLANS. THE PLANS SHOW AN ELECTRIC VALVE AND A LATERAL | | LINE AND THAT IS ALL. WHAT IS THE SIZE OF THE LINE, | | WHERE ARE THE HEADS LOCATED, IS THERE AN EXISTING | | BACKFLOW PREVENTER AND RAIN SENSOR ON THIS SYSTEM, WHAT | | IS THE SOURCE OF WATER IF NOT CITY WATER ETC. IF SO, | | PROVIDE THE LOCATION OF THE BACKFLOW DEVICE AND THE | | RAIN SENSOR AND CONTROLLER. ETC. THESE PLANS ARE | | EXTREMELY VAGUE. WPB AMEND. TO FBC SEC. 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|