Plan Review Notes For Permit 16100579 |
Permit Number |
16100579 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-01-05 15:56:34 | 2ND REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: 2ND REQEST HAS NOT COMPLIED | | | | 1. PROVIDE PLUMBING RISER DIAGRAM FOR NEW BATHROOM. PER | | WPB AMEND TO FBC 107.3.5.3(11) | | | | 3. THE PLUMBING FOR NEW MASTER BATHROOM SHALL BE TESTED | | AND THE UNDERGROUND PIPING IS TO BE INSPECTED VIA VIDEO | | CAMERA. PER FBC RES SECTION P2503 INSPECTION AND TESTS | | PLEASE PLACE NOTE ON PLAN INDICATING THIS. | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | | |
|