2016-10-26 17:17:32 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA |
| BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION |
| |
| 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS |
| |
| 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC |
| MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS |
| OF FLORIDA STATUTES |
| |
| (1) PROVIDE MECHANICAL PLANS AS PER 107.2.1.4. (SEE |
| ABOVE). |
| (2) DESIGNATE EXISTING AND NEW DUCTWORK, IF APPLICABLE. |
| (3) PROVIDE EQUIPMENT SCHEDULE AS PER R403.6.1 |
| (4) SHOW LOCATION OF CONDENSERS. |
| (5) PROVIDE CONDENSER TIE DOWN DETAIL AS PER FBC 2014 |
| (6) PROVIDE EXHAUST IN ALL BATHROOMS. |
| (7) PROVIDE RETURN FROM ALL BEDROOMS. |
| |
| FLORIDA ENERGY CODE FBC 2014 |
| |
| R403.6.1 - HEATING AND COOLING EQUIPMENT SHALL BE SIZED |
| IN ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| OTHER APPROVED HEATING AND COOLING CALCULATION |
| METHODOLOGIES, BASED ON BUILDING LOADS FOR THE |
| DIRECTIONAL ORIENTATION OF THE BUILDING. THE |
| MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR |
| UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH |
| THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN |
| CONDITIONS DESCRIBED IN |
| SECTION R302.1. THIS CODE DOES NOT ALLOW DESIGNER |
| SAFETY FACTORS, PROVISIONS FOR FUTURE EXPANSION OR |
| OTHER FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM |
| SIZING CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY |
| LOCAL INTERMITTENT MECHANICAL VENTILATION SUCH AS |
| STANDARD KITCHEN AND BATHROOM EXHAUST SYSTEMS. |
| |
| (8) PROVIDE HEAT LOAD CALCULATIONS AS PER R403.6.1 (SEE |
| ABOVE). SUMMARIES ARE NOT ACCEPTABLE. |
| |