2016-10-27 15:21:59 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] PLEASE ADDRESS BUILDING COMMENTS TO PASS THE | | ELECTRICAL REVIEW. | | | | 2] KITCHEN COUNTER TOP RECEPTACLES SHALL BE SUPPLIED BY | | NO FEWER THAN TWO SMALL APPLIANCE BRANCH CIRCUITS. | | FBC-R SECTION E3901.4 SHOW COMPLIANCE. | | | | 3] ADD A GENERAL ELECTRICAL NOTE FOR TAMPER-RESISTANT | | RECPTACLES PER FBC-R SECTION E4002.14 | | | | |
|