Plan Review Notes
Plan Review Notes For Permit 16100568
Permit Number 16100568
Review Stop E
Sequence Number 1
Notes
Date Text
2016-10-24 14:28:48ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 134 COSTELLO RD.
 DESCRIPTION: REPLACE ALL EXISTING CLOTH WIRING WITH NEW
 NM CABLE
 MASTER PERMIT: 16100568
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. SECTION 107.2.1 OF THE WPB CITY AMENDMENTS TO THE
 FBC-B REQUIRES THAT THE CONSTRUCTION DOCUMENTS BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE PROPOSED WORK AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO CODE REQUIREMENTS. (CLEARLY DEFINE YOUR
 SCOPE OF WORK ON THE PLANS). SUCH DRAWINGS SHALL
 INDICATE THE APPLICABLE DESIGN CODE, AND FURTHERMORE,
 THE DRAWINGS SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. (YOUR NAME AND
 SIGNATURE SHALL APPEAR ON ALL DOCUMENTS). THE DRAWINGS
 SHALL BE SIGNED, INCLUDE THE SCOPE OF WORK AND THE
 APPLICABLE DESIGN CODE EDITION.
 2. YOU SHALL EITHER PROVIDE A SITE PLAN OR MARK ON THE
 ELECTRICAL DRAWING THE LOCATION OF THE ELECTRICAL
 UTILITY SERVICE THE PREMISES AND INDICATE IF AERIAL OR
 UNDERGROUND. YOU SHALL ALSO MARK THE LOCATION OF THE
 ELECTRICAL METER AND MAIN DISCONNECT AS WELL AS THE
 LOCATION OF EVERY PANEL.
 3. ON THE ELECTRICAL SHEET PROVIDE A CORRECTED CIRCUIT
 DIRECTORY FOR EACH PROPERLY IDENTIFIED PANEL.
 4. NEC 408.36(D): PLUG IN TYPE OVERCURRENT PROTECTION
 DEVICES USED IN MAIN LUG ASSEMBLIES THAT ARE BACK FED
 SHALL BE SECURED IN PLACE BY ADDITIONAL FASTENER THAT
 REQUIRE OTHER THAN JUST A PULL TO RELEASE.
 5. THE SUBMITTED CIRCUIT DIRECTORIES DO NOT MATCH THE
 RISER DIAGRAM. THE RISER INDICATES A MBP AND A MLP YET
 BOTH DIRECTORIES CALL FOR MBP.
 6. THE WORD ROMEX AS USED IN THIS NOTE IS TO IDENTIFY A
 TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE OF
 CABLE, REFER TO CABLE TYPES NM, NMC OR NMS.
 7. FBC-RE3902.12/NEC 210.12B ARC-FAULT
 CIRCUIT-INTERRUPTER PROTECTION: ALL BRANCH CIRCUITS
 THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE
 OUTLETS INSTALLED IN FAMILY ROOMS, DINING ROOMS, LIVING
 ROOMS, PARLORS, LIBRARIES, DENS, BEDROOMS, SUNROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS AND SIMILAR ROOMS
 OR AREAS SHALL BE PROTECTED BY A COMBINATION TYPE
 ARC-FAULT CIRCUIT INTERRUPTER INSTALLED TO PROVIDE
 PROTECTION OF THE BRANCH CIRCUIT.
 8. FBC-ER3609.3 NEC 250.94 BONDING FOR OTHER SYSTEMS.
 THE INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
 9. FBC-RE4002.14 NEC 406.12 TAMPER-RESISTANT
 RECEPTACLES IN DWELLING UNITS. IN ALL AREAS SPECIFIED
 IN 210.52, ALL 125-VOLT, 15 AND 20 AMPERE RECEPTACLES
 SHALL BE LISTED TAMPER RESISTANT RECEPTACLES.
 10. FBC-R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
 11. FBC-R315.1 CARBON MONOXIDE PROTECTION. EVERY
 SEPARATE BUILDING OR AN ADDITION TO AN EXISTING
 BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS
 ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR
 APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER
 FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE
 AS BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL
 CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET (3048
 MM) OF EACH ROOM USED FOR SLEEPING PURPOSES.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved