2016-10-26 14:32:231ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] ACCORDING TO YOUR LOAD CALCULATION AND RISER DIAGRAM
 THE INTERIOR 100 AMP PANEL WILL HANDLE THE ENTIRE 119
 AMP LOAD OF THE HOUSE THEREFORE UNDERSIZED PER NEC
 215.2 MINIMUM RATING & SIZE OF FEEDERS. PLEASE UPGRADE
 INTERIOR PANEL OR PROVIDE A CALCULATION BREAKDOWN WITH
 PANEL SCHEDULES IDENTIFYING EACH LOAD. FBC-107
  
 2] NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.