2016-10-18 14:31:07 | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| |
| ACTION: DENIED |
| |
| 1)THE CONTRACTOR APPLICANT IS IS LICENSED AS A ALUMINUM |
| SPECIALTIES CONTRACTOR. UNLESS THIS DEMOLITION WORK IS |
| INCIDETAL TO ALUMINUM SPECIALITY WORK, A BUILDING OR |
| GENERAL CONTRACTOR IS REQUIRED TO BE THE APPLICANT. |
| PLEASE EXPLAIN HOW YOU QUALIFY TO DO THE WORK. |
| |
| 2) ALTHOUGH THE PLAN PROVIDED IS FOR REMOVAL OF DECAYED |
| ORNAMENTAL BEAMS AND IT WAS EXPLAINED BY THE APPLICANT |
| THAT AN ALTERNATE DESIGN FOR REPLACEMENT FEATURES IS |
| FORTHCOMING THE PLANS ARE INADEQUATE IN THAT THEY LACK |
| DETAIL OF WHAT EACTLY IS TO BE REMOVED AT THIS TIME. IT |
| MAY BE THAT SUCH REMOVAL CAN BE ACHIEVED WITHOUT |
| LEAVING THE BUILDING IN A VULNERABLE CONDITION, BUT THE |
| PLAN CONTAINS NO ASSURANCE OF THAT. PLEASE PROVIDE A |
| MORE DETAILED PLAN THAT IS OF SUFFICIENT CLARITY TO |
| DEMONSTRATE THE PROPOSED WORK AND THAT SUCH CAN BE |
| ACHIEVED WITHOUT LEAVING THE BUILDING IN ANY VULNERABLE |
| STATE. ADDITIONALLY, THE PLAN MUST BE OF SUFFICIENT |
| CLARITY TO BE MAINTAINED IN THE CITY RECORD MAINTENANCE |
| SYSTEM. PLEASE PROVIDE A CLEAR AND DETAILED PLAN. SUCH |
| PLAN MUST BE SIGNED BY THE PERSON TAKING RESPONSIBILITY |
| FOR THE WORK. PLEASE SEE FBC 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| ELECTRONIC MEDIA DOCUMENTS SHALL BE SUBMITTED WHEN |
| APPROVED BY THE BUILDING OFFICIAL. CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN. |
| |
| 3) PLEASE PROVIDE A SITE PLAN SHOWING THE PROPERTY |
| LINES, CONSTRUCTION AREAS, STAGING AREAS, HOW THE |
| OCCUPANTS OF THE BUILDING WILL BE SAFE GUARDED DURING |
| THEIR ENTRY AND EXIT OF THE BUILDING. SHOW COMPLIANCE |
| WITH 2014 FBC-B 3306.7 COVERED WALKWAYS INCLUDING |
| LIGHTING FO THE EXIT DISCHARGE. |
| 2014 FBC-B 3310.2 MAINTENANCE OF MEANS OF EGRESS. |
| REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED AT ALL |
| TIMES DURING CONSTRUCTION, DEMOLITION, REMODELING OR |
| ALTERATIONS AND ADDITIONS TO ANY BUILDING. |
| |
| 4) IF SCAFFOLDING EXTENDS BEYOND THE PRIVATE PROPERTY |
| AND ONTO THE DOT RIGHT OF WAY A DOT PERMIT IS REQUIRED |
| WITH REGARD TO ANY SIDEWALK CLOSURE. |
| |
| 5) IF SCAFFOLDING IS TO BE USED FOR THE HEIGHT OF THE |
| BUILDING, PLEASE PROVIDE HOW THE SCAFFOLDING WILL BE |
| BUILT AS WELL AS HOW THE SCAFFOLDING WILL BE ANCHORED |
| TO RESIST LATERAL WIND LOADING. |
| |
| 6) PLEASE BE ADVISED YOU ARE TO PROVIDE COMPLIANCE WITH |
| 2014 FBC-B 3309.1 WHERE REQUIRED. |
| ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR |
| DEMOLITION SHALL BE PROVIDED WITH NO FEWER THAN ONE |
| APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH |
| SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD |
| AS FOLLOWS: |
| |
| 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| COMBUSTIBLE MATERIALS HAVE ACCUMULATED. |
| |
| 2. IN EVERY STORAGE AND CONSTRUCTION SHED. |
| |
| 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| |
| [F] 3309.2 FIRE HAZARDS. |
| THE PROVISIONS OF THIS CODE AND THE FLORIDA FIRE |
| PREVENTION CODE SHALL BE STRICTLY OBSERVED TO SAFEGUARD |
| AGAINST ALL FIRE HAZARDS ATTENDANT UPON CONSTRUCTION |
| OPERATIONS. |
| |
| 7) DURING THE RESTORATION WORK ON THE BALCONIES HOW |
| WILL THE TENANTS BE SAFE GUARDED FROM THE WORK AREA AND |
| EGRESS ONTO THE BALCONIES? 3306.1 PROTECTION REQUIRED. |
| |
| STEVEN KENNEDY, CBO |
| CHIEF PLANS EXAMINER |