Plan Review Notes For Permit 16100404 |
Permit Number |
16100404 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-10-27 14:55:31 | 2ND REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | 1] KEN ANGELOCCI, ACCORDING TO MY CONVERSATION WITH | | PHILL PETTY OUR CHEIF ELECTRICAL INSPECTOR NO SPECIAL | | PERMISSION WILL BE GRANTED THEREFORE YOU WOULD HAVE TO | | UPGRADE THE SERVICE TO INCLUDE MAINS AS STATED IN NEC | | 230.72 (ALL MAINS MUST BE GROUPED). | | | | 2] SEMI-ADDRESSED, MISSING LABEL TO EACH METER | | ENCLOSURE IDENTIFYING THE UNIT # IT SERVES. | | | | 3] COMPLIED. | | | | 4] COMPLIED. |
|