Plan Review Notes For Permit 16100404 |
Permit Number |
16100404 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-10-20 15:21:11 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] CLARIFY IF EACH METER ENCLOSURE HAS A MAIN | | DISCONNECT ? ALL MAINS MUST BE GROUPED AT THE SERVICE | | PER NEC 230.72 | | | | 2] SHOW EXISTING SERVICE WIRE AND CONDUIT SIZES ON THE | | RISER, IDENTIFY AMPERE RATING OF EXISTING EQUIPMENT AND | | LABEL EACH DISCONNECT, PROVIDE A SITE SPECIFIC FLOOR | | PLAN INDICATING THE LOACTION OF EACH PANEL. | | FBC-107.3.5.3 | | | | 3] MISSING 2 SMALL APPLIANCE VA LOADS ON THE | | CALCULATION, ASWELL AS THE WASHER CIRCUIT. IF THE | | BUILDING HAS A COMMON LAUNDRY PLEASE SPECIFY ON THE | | CALCS. NEC 220.52(A)&(B) | | | | 4] ACCORDING TO NEC 220.82 OPTIONAL FEEDER AND SERVICE | | LOAD CALCULATIONS ONLY APPLY TO 120-240 VOLTS 3 WIRE | | CONDUCTORS WITH AN AMPACITY OF 100 AMP OR GREATER. | | ( YOUR LOAD SIZE IS 70 AMPS THEREFORE YOU MUST USE THE | | STANDARD METHOD IN ACCORDANCE WITH NEC 220 PART 3 ) | | | | |
|