 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE APPEAR TO BE SOME ERRORS IN THE ENERGY FORMS.
 THE PLANS FOR THE ADDITION SPECIFY A ONE FOOT OVERHANG
 AND THE FORMS LIST A TWO FOOT OVERHANG. THE PLANS SHOW
 A FLAT SINGLE ASSEMBLY ROOF ON THE ADDITION WITH A
 MODIFIED BITUMEN ROOF SYSTEM AND THE ENERGY FORMS
 SPECIFY A HIP ROOF WITH A FULL ATTIC AND COMPOSITE
 SHINGLES. ALL OF THE WINDOWS IN THE ADDITION FACE EAST
 AND THE FORMS LIST ONE FACING NORTH. PLEASE MAKE SURE
 THAT THE INFORMATION LISTED IN THE FORMS MATCH THE
 PLANS, FBC ENERGY CONSERVATION SECTION 405
  
 2) THE MECHANICAL PLANS SPECIFY THAT THE DUCTWORK WILL
 BE IN THE CEILING. THE PLANS SPECIFY A SINGLE ASSEMBLY
 FLAT ROOF AND DO NOT SHOW ANY SOFFITS FOR THE DUCTWORK.
 COORDINATE THE MECHANICAL WITH THE ARCHITECTURAL PLANS.
 FBC 107.2.1
  
 3) THE EQUIPMENT SIZING CALCULATIONS INDICATE THAT A
 ONE TON COOLING UNIT IS ADEQUATE. JUSTIFY WHY A 1.5 TON
 IS PROPOSED. THE ACTUAL TOTAL BTUH IS MORE THAN 1.15
 TIMES THE REQUIRED BTUH. FBC ENERGY CONSERVATION
 SECTION 403.6.1.1
  
  
  
  