2016-11-29 18:02:00 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THERE APPEAR TO BE SOME ERRORS IN THE ENERGY FORMS. | | THE PLANS FOR THE ADDITION SPECIFY A ONE FOOT OVERHANG | | AND THE FORMS LIST A TWO FOOT OVERHANG. THE PLANS SHOW | | A FLAT SINGLE ASSEMBLY ROOF ON THE ADDITION WITH A | | MODIFIED BITUMEN ROOF SYSTEM AND THE ENERGY FORMS | | SPECIFY A HIP ROOF WITH A FULL ATTIC AND COMPOSITE | | SHINGLES. ALL OF THE WINDOWS IN THE ADDITION FACE EAST | | AND THE FORMS LIST ONE FACING NORTH. PLEASE MAKE SURE | | THAT THE INFORMATION LISTED IN THE FORMS MATCH THE | | PLANS, FBC ENERGY CONSERVATION SECTION 405 | | | | 2) THE MECHANICAL PLANS SPECIFY THAT THE DUCTWORK WILL | | BE IN THE CEILING. THE PLANS SPECIFY A SINGLE ASSEMBLY | | FLAT ROOF AND DO NOT SHOW ANY SOFFITS FOR THE DUCTWORK. | | COORDINATE THE MECHANICAL WITH THE ARCHITECTURAL PLANS. | | FBC 107.2.1 | | | | 3) THE EQUIPMENT SIZING CALCULATIONS INDICATE THAT A | | ONE TON COOLING UNIT IS ADEQUATE. JUSTIFY WHY A 1.5 TON | | IS PROPOSED. THE ACTUAL TOTAL BTUH IS MORE THAN 1.15 | | TIMES THE REQUIRED BTUH. FBC ENERGY CONSERVATION | | SECTION 403.6.1.1 | | | | | | | | |
|