2016-10-24 09:51:001ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 PASSED WITH THE FOLLOWING PROVISO'S (RED-LINED ON
 PLANS)
  
 1] AFCI PROTECTION REQUIRED PER FBC-R SEC E3902.12.
 2] CARBON MONOXIODE ALARMS REQUIRED IN ACCORDANCE WITH
 FBC-R SEC 315.
 3] SMOKE ALARMS SHALL BE 3' AWAY FROM AC & BATH AS
 STATED IN NFPA 72 SEC 29.8.3.4.
  