2016-11-29 19:12:32 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) IN ORDER TO PROVIDE VENTILATION TO THE THE SINGLE |
| ASSEMBLY ROOF SYSTEM, A CONTINOUS SOFFIT VENT WOULD BE |
| REQUIRED. FBC-R806.1 |
| |
| 2) THE SINGLE ASSEMBLY ROOF SYSTEM HAS 2 X 8 RAFTERS, |
| WHICH WILL HAVE A SPACE OF 7.25 INCHES. THIS WOULD NOT |
| BE ENOUGH SPACE FOR THE R-30 INSULATION AND A ONE INCH |
| AIR SPACE. FBC-R 806.3 |
| |
| 3) THE SIGNED AND SEALED ENHANCED FASTENING |
| CALCULATIONS FOR THE TAMKO MODIFIED ROOF SYSTEM DO NOT |
| SPECIFY THE NOA PAGE NUMBER, THE SYSTEM TYPE OR TYPE OF |
| FASTENERS THAT WILL BE USED. THERE ARE TWO PAGES IN THE |
| NOA FOR SYSTEMS WITH NON-INSULATED DECKS WHICH HAVE A |
| MAXIMUM DESIGN PRESSURE OF -60PSF. HOWEVER, NEITHER ONE |
| OF THEM HAS FASTENER SPACING OF 11" ON CENTER. NOTE: |
| OPTION #1 ON PAGE 13 USES RING SHANK NAILS AND TIN CAPS |
| WITH A MAXIMUM DESIGN PRESSURE OF -52.5 PSF. |
| |
| 4) THE MECHANICAL PLANS SHOW DUCT WORK IN AN ATTIC. THE |
| ADDITION HAS A SINGLE ASSEMBLY ROOF WITH NO ROOM FOR |
| DUCTS. COORDINATE THE ARCHITECTURAL PLANS WITH THE |
| MECHANICAL PLANS TO ADDRESS THIS ISSUE. FBC 107.2.1 |
| |
| 5) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |
| |