Plan Review Notes
Plan Review Notes For Permit 16100387
Permit Number 16100387
Review Stop B
Sequence Number 1
Notes
Date Text
2016-11-29 19:12:32PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IN ORDER TO PROVIDE VENTILATION TO THE THE SINGLE
 ASSEMBLY ROOF SYSTEM, A CONTINOUS SOFFIT VENT WOULD BE
 REQUIRED. FBC-R806.1
  
 2) THE SINGLE ASSEMBLY ROOF SYSTEM HAS 2 X 8 RAFTERS,
 WHICH WILL HAVE A SPACE OF 7.25 INCHES. THIS WOULD NOT
 BE ENOUGH SPACE FOR THE R-30 INSULATION AND A ONE INCH
 AIR SPACE. FBC-R 806.3
  
 3) THE SIGNED AND SEALED ENHANCED FASTENING
 CALCULATIONS FOR THE TAMKO MODIFIED ROOF SYSTEM DO NOT
 SPECIFY THE NOA PAGE NUMBER, THE SYSTEM TYPE OR TYPE OF
 FASTENERS THAT WILL BE USED. THERE ARE TWO PAGES IN THE
 NOA FOR SYSTEMS WITH NON-INSULATED DECKS WHICH HAVE A
 MAXIMUM DESIGN PRESSURE OF -60PSF. HOWEVER, NEITHER ONE
 OF THEM HAS FASTENER SPACING OF 11" ON CENTER. NOTE:
 OPTION #1 ON PAGE 13 USES RING SHANK NAILS AND TIN CAPS
 WITH A MAXIMUM DESIGN PRESSURE OF -52.5 PSF.
  
 4) THE MECHANICAL PLANS SHOW DUCT WORK IN AN ATTIC. THE
 ADDITION HAS A SINGLE ASSEMBLY ROOF WITH NO ROOM FOR
 DUCTS. COORDINATE THE ARCHITECTURAL PLANS WITH THE
 MECHANICAL PLANS TO ADDRESS THIS ISSUE. FBC 107.2.1
  
 5) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  