Plan Review Notes
Plan Review Notes For Permit 16100310
Permit Number 16100310
Review Stop G
Sequence Number 1
Notes
Date Text
2016-10-20 09:34:051) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE
 THAT WERE USED IN THE DESIGN OF THIS SYSTEM. FGC
 SEC.402.3, FBCR SEC. G 2413.3.
 2) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
 3) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 4)SHOW THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
 5) SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (REGULATOR / LP TANK) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
 6) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF ALL THE
 GAS APPLIANCES. WPB AMEND. TO FBC SEC. 107.2.1.
 7) THE PROPOSAL FROM APS REFERS TO THE INSTALLATION OF
 A COOKTOP/RANGE AND A TANKLESS WATER HEATER IN ADDITION
 TO THE GENERATOR AND THE BBQ. THIS INFO IS NOT ON THE
 APPLICATION AND THESE APPLIANCES ARE NOT SHOWN ON THE
 PLANS.
 8) SUBMIT A GAS RISER THAT SHOWS ALL OF THE GAS
 APPLIANCES/EQUIPMENT ON THE RISER. WPB AMEND. TO FBC
 SEC. 107.2.1.
 9) SHOW THE DISTANCE OF THE LP TANK FROM THE PROPERTY
 LINE.
 10) SHOW THE SIZE AND TYPE OF PIPE/TUBING FROM THE LP
 TANK TO THE FIRST STAGE REGULATOR.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  