Plan Review Notes For Permit 16100310 |
Permit Number |
16100310 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-10-18 15:15:28 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THERE IS INSUFFICIENT DETAIL INDICATED TO DETERMINE | | COMPLIANCE WITH FIRE AND LIFE SAFETY STANDARDS. | | | | | | 1) IS THE TANK UNDER OR ABOVE GROUND? THERE IS NO | | DETAIL INDICATING EITHER INCLUDING DEPTH OF COVER, SLAB | | SIZE, TIE DOWN TYPE, SPECS, DOUBLE WALLED, ETC. | | | | | | | | 2) THERE IS NO INDICATION WHAT FIRE CODE IT IS | | COMPLIANCE WITH. THE INSTALLATION SHALL COMPLY WITH | | NFPA 58 AND/OR OTHER APPLICABLE CODES. | | | | PLEASE PROVIDE A NOTE OF ACKNOWLEGEMENT OF FIRE CODE | | COMPLIANCE. | | | | | | | | 3) THERE IS NO ACTUAL INDICATION OF DISTANCE FROM ALL | | PROPERTY LINES AND BUILDINGS. | | | | PLEASE PROVIDE DIMENSIONS OF ALL APPLICABLE AREAS PER | | NFPA SEPARATION REQUIREMENTS. | | | | | | | | | | 4) PLEASE PROVIDE PLAN SHEET REVISION CLOUDS OR | | NUMBERED NARRATIVE RESPONSES TO THE ABOVE. | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|