2016-10-13 09:38:42 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- FLAT ROOF: | | THE DESIGN PRESSURE OF THE SELECTED APPROVED ASSEMBLY | | FORM NOA 14-05296.02 SUBMITTED IS -52.5 PSF. NEED TO | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | REQUIRED BY GENERAL LIMITATION #7 TO MEET THE DESIGN | | PRESSURE OF SEC. R301.1 FBC-RESIDENTIAL, 5TH EDITION | | (2014). SEE GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | SUBMITTED. | | | | 2- SPECIFY THE SHINGLES ROOF PITCH. SEC. R905.2.2 | | FBC-RESIDENTIAL. | | | | 3- SPECIFY TOTAL SHINGLES AREA AND TOTAL FLAT ROOF AREA | | TO VERIFY VALUATION. SEC. 109.3 CITY AMENDMENTS., | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] | | |
|