2016-10-31 18:26:11CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 (1) PROVIDE ON EQUIPMENT SCHEDULE WHICH HVAC SYSTEM IN
 BUILDING WILL PROVIDE THE 1107 CFM TO INSURE OVERALL
 BUILDING BALANCE IS POSITIVE.
 (2) PROVIDE SEQUENCE OF OPERATION SHOWING SAID MAKE UP
 AIR BUILDING HVAC SYTEM SHUTS DOWN WHEN HOOD IS IN
 ALARM.
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]