Plan Review Notes
Plan Review Notes For Permit 16100212
Permit Number 16100212
Review Stop M
Sequence Number 1
Notes
Date Text
2016-10-13 18:54:09CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC
 MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS
 OF FLORIDA STATUTES.
  
 (1) PROVIDE EQUIPMENT SCHEDULE AS PER R403.6.1.
 (2) PROVIDE LOCATION OF CONDENSER ON EXTERIOR OF BLDG.
 (3) CONFIRM INSULATION R VALUE. PLANS SHOW R8. DUCT
 INSULATION IS USUALLY R6.
 (4) BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. SEE ABOVE 107.2.1.4.
 (5) SHOW ON PLANS ALL BATH EXHUST.
  
 FLORIDA ENERGY CODE FBC 2014
  
 (6) PROVIDE AHRI FOR EQUIPMENT ON PLANS. PLANS SHOW (2)
 2 TON SYSTEMS.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  