2016-11-15 09:05:08 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC FIFTH EDITION (2014) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE WORK AREA EXCEEDS 50 PERCENT OF THE AGGREGATE |
| AREA OF THE STRUCTURE. THEREFORE, THIS PROJECT IS A |
| LEVEL 3 ALTERATION PER FBC EXISTING BUILDING SECTION |
| 505.1. |
| |
| 2) FBC-R310.1 EMERGENCY ESCAPE AND RESCUE REQUIRED. |
| BASEMENTS, HABITABLE ATTICS AND EVERY SLEEPING ROOM |
| SHALL HAVE AT LEAST ONE OPERABLE EMERGENCY ESCAPE AND |
| RESCUE OPENING. SPECIFY THE TYPE AND THE SIZE OF THE |
| WINDOWS IN BEDROOM NUMBER 3 TO SHOW THAT THEY MEET THE |
| REQUIREMENTS OF FBC-R310.1, R301.1.1, R301.1.2 & |
| R301.1.3. |
| |
| 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT |
| APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION |
| INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF |
| THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES, |
| STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES. THE |
| PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE CGI |
| MULLIONS WITH NOA NO. 15-0420.07 IS NOT LISTED IN THE |
| PRODUCT APPROVAL SCHEDULE ON SHEET 2 AND DOES NOT HAVE |
| A SHOP REVIEW STAMP FROM THE DESIGNER OF RECORD. |
| |
| 4) THE PLANS ARE LABELED PHASE 1 AND PHASE 2. SINCE |
| THEY WERE BOTH SUBMITTED UNDER THE SAME PERMIT NUMBER |
| ALL OF THE WORK SHOWN FOR BOTH PHASES WILL NEED TO BE |
| COMPLETED BEFORE A FINAL INSPECTION CAN BE APPROVED AND |
| A CERTIFICATE OF COMPLETION ISSUED. FBC 111.4 |
| |
| 5) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |
| |