Plan Review Notes For Permit 16100179 |
Permit Number |
16100179 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-10-12 11:25:41 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16100179 | | 10/12/16 | | | | 1) THE PLANS MUST BEAR THE ORIGINAL SIGNATURE AND SEAL | | AND TITLE BLOCK OF THE ENGINEER JOHN P. REED- SECTION | | 61G15-23.002 FLORIDA ADMINISTRATIVE CODE. | | | | 2) A REVISION TO THE APPROVED ARCHITECTURAL, MECHANICAL | | AND ELECTRICAL PLAN SHEETS ARE REQUIRED TO SHOW THE | | CHANGE TO THE UNDERGROUND EXHAUST SYSTEM, AND THE | | CHANGE MUST BE APPROVED WITH SIGNATURES BY THE DESIGN | | PROFESSIONALS OF RECORD. | | | | 3) REFER TO SECTION 603.8.3 AND VERIFY THE UNDERGROUND | | PVC DUCTS ARE IN COMPLIANCE WITH THE ASTM D2412 TESTING | | STANDARD. | | | | 4) REFER TO SECTION 603.18.1 AND VERIFY STRUCTURAL | | COMPLIANCE FOR THE FLOOR FITTINGS. | | | | 5) THE PLAN APPEARS TO INDICATE THAT THE BLOWER FOR THE | | EXHAUST SYSTEM IS DISCHARGING INTO THE EQUIPMENT ROOM. | | PLEASE NOTE PER SECTION 501.1 EXHAUST SHALL DISCHARGE | | TO THE OUTDOORS AT A POINT WHERE IT WILL NOT CAUSE A | | NUISANCE AND NOT LESS THAN THE DISTANCES SPECIFIED IN | | SECTIION 501.3.1. | | | | 6) CLARIFY HOW THE BLOWER SIZE WAS DETERMNINED- SHOW | | CALCULATUIONS. | | | | 6) THE KEY NOTE 20 IN A HEX SYMBOL IS SHOWN IN MANY | | PLANCES ON THE PLAN WITH NO EXPLANATION OF WHAT IT IS | | INDICATING- PLEASE CLAIFY. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|