2016-10-12 11:25:411ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16100179
 10/12/16
  
 1) THE PLANS MUST BEAR THE ORIGINAL SIGNATURE AND SEAL
 AND TITLE BLOCK OF THE ENGINEER JOHN P. REED- SECTION
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.
  
 2) A REVISION TO THE APPROVED ARCHITECTURAL, MECHANICAL
 AND ELECTRICAL PLAN SHEETS ARE REQUIRED TO SHOW THE
 CHANGE TO THE UNDERGROUND EXHAUST SYSTEM, AND THE
 CHANGE MUST BE APPROVED WITH SIGNATURES BY THE DESIGN
 PROFESSIONALS OF RECORD.
  
 3) REFER TO SECTION 603.8.3 AND VERIFY THE UNDERGROUND
 PVC DUCTS ARE IN COMPLIANCE WITH THE ASTM D2412 TESTING
 STANDARD.
  
 4) REFER TO SECTION 603.18.1 AND VERIFY STRUCTURAL
 COMPLIANCE FOR THE FLOOR FITTINGS.
  
 5) THE PLAN APPEARS TO INDICATE THAT THE BLOWER FOR THE
 EXHAUST SYSTEM IS DISCHARGING INTO THE EQUIPMENT ROOM.
 PLEASE NOTE PER SECTION 501.1 EXHAUST SHALL DISCHARGE
 TO THE OUTDOORS AT A POINT WHERE IT WILL NOT CAUSE A
 NUISANCE AND NOT LESS THAN THE DISTANCES SPECIFIED IN
 SECTIION 501.3.1.
  
 6) CLARIFY HOW THE BLOWER SIZE WAS DETERMNINED- SHOW
 CALCULATUIONS.
  
 6) THE KEY NOTE 20 IN A HEX SYMBOL IS SHOWN IN MANY
 PLANCES ON THE PLAN WITH NO EXPLANATION OF WHAT IT IS
 INDICATING- PLEASE CLAIFY.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER