2016-10-25 07:30:52 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16100165 |
| ADD: 255 EVERNIA ST. SUITE # 1519 |
| CONT: ALL FLAGS CONSTRUCTION |
| TEL: 561-312-7675 |
| E-MAIL: STEVE @ ALLFLAGSCONSTRUCTION.COM |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. OCT. 25/2016 |
| ACTION: DENIED |
| |
| 1) SHEET A-1.01 NOTE 11 INDICATES THE REMOVAL OF ALL |
| FLOOR TILE AND WOOD FLOORING AND INSULATION, THE PLANS |
| DO NOT INDICATE WHAT MATERIAL IS TO BE RE-INSTALLED. |
| THE STRAND IS DOCUMENTED AS HAVING 8 INCH CONCRETE |
| FLOOR SLABS, EITHER TEST REPORTS FOR 6 INCH AND 8 INCH |
| FLOOR SLABS ARE ACCEPTED. SEE SOUND INSULATION |
| REQUIREMENTS LISTED BELOW. |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2014) |
| FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| 1A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 1B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 1C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |