Plan Review Notes For Permit 16100149 |
Permit Number |
16100149 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-10-12 06:45:20 | 1) SHOW THE APPROXIMATE LOCATION OF THE INTERCEPTOR ON | | THE SITE PLAN. WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER TO | | ENSURE THE NEW INTERCEPTOR IS SIZED PROPERLY. 2014 FPC | | SEC. 1003.2. CONTACT LEE SCHNEEWEISS FROM SCHIER AT | | 1-800-538-4792. | | 3) WHAT SIZE GREASE INTERCEPTOR IS THIS REPLACING? | | INNDICATE ON THE SITE PLAN. | | 4) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE OF THE | | INTERCEPTOR. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|