2016-10-11 16:32:251ST REVIEW FBC-2014 BUILDING
 PERMIT #16100125
 10/11/16
  
 1) THE SUBMITTED CALCULATIONS AND UPLIFT ZONE SCHEMATIC
 DRAWING FROM ATLAS STRUCTURAL ENGINEERING LLC EACH MUST
 BEAR THE ORIGINAL SIGNATURES AND SEALS OF THE EINGINEER
 OF RECORD PER FLORIDA STATUE AND SECTION 61G15-23.002
 FAC.
  
 2) REFER TO GENERAL LIMITATION NOTE #5 OF NOA
 13-1113.03 AND PROVIDE THE PULL TEST RESULTS.
  
 3) PROVIDE ENLARGED DRAWINGS OF EACH ROOF SECTION
 SHOWING THE LOCATIONS OF EXISTING ROOF DRAINS AND
 SCUPPERS AND ALL ROOFTOP MECHANICAL EQUIPMENT. A)
 PROVIDE A SCOPE OF WORK FOR THE ROOFTOP EQUIPMENT-
 CLARIFY IF ANY EQUIPMENT, STANDS, OR CURBS ARE BEING
 TEMPORARILY REMOVED, OR REPLACED DURING THE REROOFING
 PROCESS.
  