Plan Review Notes For Permit 16100125 |
Permit Number |
16100125 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-10-11 16:32:25 | 1ST REVIEW FBC-2014 BUILDING | | PERMIT #16100125 | | 10/11/16 | | | | 1) THE SUBMITTED CALCULATIONS AND UPLIFT ZONE SCHEMATIC | | DRAWING FROM ATLAS STRUCTURAL ENGINEERING LLC EACH MUST | | BEAR THE ORIGINAL SIGNATURES AND SEALS OF THE EINGINEER | | OF RECORD PER FLORIDA STATUE AND SECTION 61G15-23.002 | | FAC. | | | | 2) REFER TO GENERAL LIMITATION NOTE #5 OF NOA | | 13-1113.03 AND PROVIDE THE PULL TEST RESULTS. | | | | 3) PROVIDE ENLARGED DRAWINGS OF EACH ROOF SECTION | | SHOWING THE LOCATIONS OF EXISTING ROOF DRAINS AND | | SCUPPERS AND ALL ROOFTOP MECHANICAL EQUIPMENT. A) | | PROVIDE A SCOPE OF WORK FOR THE ROOFTOP EQUIPMENT- | | CLARIFY IF ANY EQUIPMENT, STANDS, OR CURBS ARE BEING | | TEMPORARILY REMOVED, OR REPLACED DURING THE REROOFING | | PROCESS. | | | | CHRISTOPHER L. COLE | | BUILDING PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|